900字范文,内容丰富有趣,生活中的好帮手!
900字范文 > 电压互感器互投装置 potential transformer Change-over equipment英语短句 例句大全

电压互感器互投装置 potential transformer Change-over equipment英语短句 例句大全

时间:2020-03-28 15:30:34

相关推荐

电压互感器互投装置 potential transformer Change-over equipment英语短句 例句大全

电压互感器互投装置,potential transformer Change-over equipment

1)potential transformer Change-over equipment电压互感器互投装置

1.Thepotential transformer Change-over equipment, which installed in the 27.5KV母线电压互感器互投装置就是一种老设备,它仍然使用普通的电压继电器组合而成,可靠性差。

英文短句/例句

1.Research and Development of Traction Substation Potential Transformer Change-Over Equipment Base on GPRS Communications基于GPRS通信的牵引变电所电压互感器互投装置的研究与开发

2.Design on the Transformers Automatic Switching Device in 220KV Transformer Substations;220KV变电站变压器互投装置的设计

3.Research on Current Transformer Configuration of 220kV Transformer Failure Protection220kV变压器失灵保护装置电流互感器配置研究

4.Study of Dynamic Compensaing Equipment of the Secondary Voltage Drop of Voltage Transformer;电压互感器二次压降动态补偿装置的研究

5.Automatic compensation equipment for PT secondary voltage drop电压互感器二次回路压降的自动补偿装置

6.Voltage transformersGB1207-1997电压互感器

7.The Capacitor Configuration of GIS Potential Transformer on the Spot TestGIS电压互感器就地检定的电容配置

8.high voltage current transformer & potential transformer高压电流电压互感器

9.Influence of Incorrect Connections for Voltage Transformer on Metering Devices and Preventative Measures电压互感器二次接线错误对计量装置的影响及防范措施

10.Some Common Problems in the Use of the Apparatus for On-site Calibration of HLEI-type Current TransformatorHLE1型电流互感器现场检定装置现场检定电流互感器的常见问题

11.dual purpose voltage transformer双重用途电压互感器

12.rated transformation ratio (of a voltage transformer)(电压互感器的)额定变比

13.rated transformation ratio of voltage transformer电压互感器的额定变比

14.unearthed voltage transformer不接地型电压互感器

15.actual transformation ratio of voltage transformer电压互感器的实际变化

16.gle of a voltage transformer电压互感器的相角差

17.Laser Power Supplies, Module Power Supplies, Fully-encapsulated Power/ Voltage/ Current Transformers.固体激光电源、导体激光电源、块电源、装式电源变压器、压电流互感器。

18.high voltage capacitor(of a capacitor voltage transformer)电容器式电压互感器的高压电容器

相关短句/例句

configuration of PT电压互感器配置

3)potential transformer电压互感器

1.Measures preventing from iron core magnetic resonance caused by iron core saturation ofpotential transformer;电压互感器铁心饱和引起铁磁谐振的防治措施

2.Single-phase check methed ofpotential transformer for on-site check;电压互感器现场校验的单相校验法

3.Time-domain measuring method for wide-frequency transfer characteristic ofpotential transformer;电压互感器宽频传递特性的时域测量方法

4)Voltage mutual inductor电压互感器

1.Voltage Mutual Inductor Grounding and Its Function in Transformer Substation;变电站的电压互感器接地方式及功能

2.Taking the case of voltage mutual inductor exploration of TYD-110/3-0.02H电压互感器的爆炸事故为例,对该设备的故障原因进行分析,并对设备的检修试验、采购选型、运行巡视3方面提出了一些预防措施和建议。

3.Ferromagnetic resonance of voltage mutual inductors for 6 kV power supply system of the oil refinery took place several times, resulting in burn- out of voltage mutual inductors of 6 kV substation, explosion of lightning guards, breakdown of electric equipment, fusing of high voltage fuses and misoperation of relaying protection.针对炼油厂6kV供电系统运行中多次发生电压互感器铁磁谐振,导致6 kV配电所电压互感器烧毁,避雷器爆炸,用电设备击穿,高压熔断器熔断,造成继电保护误动等问题进行了原因分析,提出了预防措施。

5)voltage transformer电压互感器

1.Site test and analysis of 220 kV metricalvoltage transformer;220kV计量电压互感器的现场测试及分析

2.Analysis ofvoltage transformer secondary loop grounding point;电压互感器二次回路接地点分析

3.Verifying the voltage ratio ofvoltage transformer (discharge coil) by method of adding the high voltage;采用高压加压法校核电压互感器(放电线圈)变比

6)PT[英][,pi: "ti:][美]["pi "ti]电压互感器

1.Harm done by the failure of the circuitryPT to the power system;线路电压互感器故障对系统造成的危害

2.PT Secondary Circuit Reducing Reform and its Reducing Mothod;电压互感器二次回路压降改造及减少压降的方法

3.Analysis and Solution of the 6~10 kV Power Distribution GridPT Resonance Elimination6~10kV配电网电压互感器消谐的分析及对策

延伸阅读

电力系统电压互感器谐振过电压电力系统电压互感器谐振过电压resonance overvoltage due to potential transformer in electric power system南定理,可将三相对地电容等效连接在电撅变压器和互感器的两个中性点之间,由此着出,谐振属于零序性质。无论是电源合闸至空载母线所引起的电压互感器的涌流现象,还是线路中发生对地闪络和熄弧后C。中残余电荷经电压互感器放电所引起的磁饱和现象,都会在一定的C0值下激发起谐振过电压,它表现为电力系统中性点发生位移,并全部反映至开口三角形绕组,引起虚幻的接地故障信号。这是配电网中造成故障最多的一种内部过电压. 图1中性点不接地系统中三相电压 互感器接线图和等效谐振回路(a)三相电压互感导接线图;(b)等效谐振回路由于谐振的零序性质,导线的相间电容、余弦电容器和传愉的三相有功负荷均对谐振不起作用。随着C。的增加(即导线增长),将依次发生高频、工频和分频谐振。在很短的空母线合闸时,C0很小,会产生3倍以上的高频谐振过电压。较大的c0则会出现工频谐振过电压,此时一相对地电压很低,其它两相的对地电压接近于线电压,故工频谐振和单相接地现象往往难以区别。当母线上的出线较长时,C。很大将会发生分频谐振,其频率略低于电源颇率的一半,电压表的指针会发生低频摆动,谐振电压分t和开口三角形电压接近于相电压,由于此时谐振频率和相应的励磁感抗减半,互感器趋于深度磁饱和,励磁电流急剧增大,高达额定值的数十倍以至百倍以上,从而造成互感器的发热、喷油以至爆炸。在高频和分频谐振时,三相对地电压同时升高。可以通过两种途径来抑制上述谐振现象.其一是采取阻尼吸能措施,即在开口三角形绕组两端临时并接一个低值电阻(在6一10kV小电网中,可用200~50ow的白炽灯泡)或将互感器高压中性点经大电阻接地。其二是破坏谐振条件,即人为地增大对地电容使之超过某一临界值,或将开口三角形绕组临时短接,或将互感器高压中性点临时不接地,或将电网改为通过消弧线圈接地。d旧nl一x一tongd旧nyo hugonq一x旧zhen guod{anyo电力系统电压互感公谐振过电压(resonanceovervoltage due to potential transformer inelectrie power system)电磁式电压互感器由于铁芯磁饱和引起的铁磁谐振过电压。在中性点不接地和直接接地电力系统中均有可能发生.中性点不接地系统中电压互感器的谐振过电压图1中电源变压器的中性点不接地,电压互感器的中性点直接接地,其励磁电感La、L。和Lc分别与导线和母线的对地电容C。相并联而形成谐振回路。

本内容不代表本网观点和政治立场,如有侵犯你的权益请联系我们处理。
网友评论
网友评论仅供其表达个人看法,并不表明网站立场。